Industrial Battery Charger (DC UPS)

Product Overview
Borna Electronics Industrial Battery Chargers (DC UPS) have been manufactured since 1996 and are widely used in oil & gas, petrochemical, mining, steel, and power generation industries. The latest generation incorporates a thyristor rectifier and an advanced booster stage to achieve a power factor of up to 0.98 and input current THD below 5% in accordance with IEEE-519.

Key Features

  • Available with single-phase or three-phase input
  • Available in 6-pulse and booster-equipped versions
  • Output current up to 1000 A
  • Constant Voltage (CV) and Constant Current (CC) operating modes
  • Initial, Float, Boost, and Automatic charging modes
  • Suitable for Lead-Acid, Ni-Cd, and Lithium batteries
  • Heavy-duty industrial design

Functions & Capabilities

  • Isolation transformer
  • Microcontroller-controlled full-wave thyristor rectifier
  • Current limiting unit
  • HMI touch panel or LCD Mimic Diagram interface
  • Timed Boost charging mode
  • Input overvoltage and undervoltage protection
  • Reverse battery connection protection
  • Leakage current protection
  • Temperature-compensated charging voltage
  • RS-485 communication
  • Alarm and fault display
  • Storage of more than 400 fault records
  • Dropper unit or optional DC/DC module
  • EMI filters on input and battery circuits

Technical Specifications

ParameterSpecification
StandardsDIN 41773, NEMA PE 5-1997 (R2003), IPS-M-EL-174(2)
Output Voltage24VDC, 48VDC, 110VDC, 220VDC
Power Factor0.98
Efficiency94%
Operating Temperature-10°C to +40°C
AltitudeUp to 1000 m
HumidityUp to 90%
Input220 VAC Single Phase or 380 VAC Three Phase + Neutral
Input Voltage Tolerance±15%
Input Frequency50 Hz ±5%
Battery TypesLead-Acid, Ni-Cd, Lithium
Protection DegreeIP21 to IP54
Noise Level<65 dB at 1 m
CoolingForced Air Cooling / Optional Natural Air Cooling