Where an insulating flange kit separates pipeline sections, induction or lightning can create a large potential difference across the flange and damage the insulation.
Zinc anodes are used as earth electrodes at these points. A zinc earthing cell ZEC dampens large, sudden currents and provides an earth connection, causing some loss of protection current. Zinc also naturally acts as an anode and slightly improves the potential drop.

Zinc Earthing Cell Connection to a Pipeline and Ground Installation
These electrodes have the composition of soil-service zinc anodes and are manufactured to ASTM B418 Type II. Cells may be single, double or quadruple, with individual electrodes insulated from one another. Like soil anodes, they are surrounded by backfill, usually 75% gypsum, 20% bentonite and 5% sodium sulphate.
The connection uses copper cable with a cross-section of 10 mm² or 16 mm² welded to the steel core inside the electrode. The copper-cable-to-steel connection is covered with epoxy resin.
Zinc Earthing Cell Dimensions and Weight
| Weight Single / double / quadruple (kg) | Length(mm) | Width(mm) | Altitude (mm) |
| 11/22/44 | 914 | 40 | 40 |
| 10/20/40 | 1525 | 30 | 30 |
| 13/26/52 | 1525 | 36 | 36 |
| 17/34/68 | 1525 | 40 | 40 |
| 22/44/88 | 1525 | 45 | 45 |