Transformer Rectifiers

Transformer rectifiers supply current to protected structures in impressed current cathodic protection systems. They rectify incoming AC and inject and stabilise protection current. Units are manufactured for continuous full-load operation in humid, dusty, saline, electrical-room and other environments, with the following conditions:

  • Maximum temperature under a sunshade: 50 °C
  • Maximum temperature of metal surfaces exposed directly to sunlight: 80 °C
  • Maximum relative humidity: 95%
  • Thunderstorm level: 60 days per year
  • Approximate dust concentration: 70 to 1400 mg/m³

Transformer Rectifier Cooling Types

  • Natural Air Cooling AN

These units are normally manufactured for 10–50 V and 5–30 A. Higher-power air-cooled units can be designed and manufactured on request.

  • Natural Oil Cooling ON

Oil cooling improves reliability in harsh conditions. The rectifier bridge and filters are immersed in oil. The tank has oil-level and temperature indicators and a moisture absorber.

Transformer Rectifier Control Methods

  • Autotransformer Controlled Regavolt Transformer Rectifiers

Autotransformer Controlled Regavolt Transformer Rectifiers

Available with single-phase or three-phase input, these units have a variable autotransformer variac in the main transformer’s primary circuit. It adjusts primary voltage from zero to maximum, and thus secondary voltage from zero to rated maximum. With a diode bridge, the rectified output voltage is adjustable in the same way.

The advantage is continuous output-voltage adjustment from zero to rated maximum. These are constant-voltage units: voltage is adjusted to obtain the required current. Their main drawback is that changes in equivalent system resistance, caused by rain, dry soil or other conditions, change the current while voltage remains at its setting, requiring readjustment.

  • Electronically Controlled Transformer Rectifiers

These use a thyristor bridge, normally full-wave and either semi-controlled or fully controlled, on the step-down transformer secondary. The electronic controller changes thyristor firing angle to adjust output power.

Depending on requirements and operating conditions, thyristor rectifiers can use current-source or voltage-source control.

  • Constant Voltage

The controller uses output-voltage feedback to hold the preset voltage despite input-voltage or output-current changes. Like autotransformer units, a fall in current caused by higher soil resistivity can leave the structure underprotected, while increased current caused by lower equivalent resistance can damage its coating.

  • Constant Current

Electronically controlled constant-current AMP-O-MATIC units reduce the inspection and adjustment needs of constant-voltage equipment. When system resistance changes, current remains constant and output voltage changes. If resistance rises, voltage rises proportionally to maintain the injected current. The controller samples output current through a shunt, detects deviations and changes thyristor firing angle to restore the setting. If environmental changes, such as seasonal variation, increase system resistance, output voltage can rise to 10% above the unit’s rated voltage to maintain the set current.

Borna Electronic air-cooled multichannel electronically controlled transformer rectifiers

  • Electronic and Autotransformer Controlled Transformer Rectifiers Automatic and Manual

This combined design improves reliability by maintaining output if the electronic controller develops a fault. Cathodic protection units are often installed in harsh climates and remote locations, where repairs take time and loss of protection can cause irreparable damage. The combined system is economical in these conditions: if electronic control fails, the unit continues operating through its autotransformer.

A variac is installed in the main transformer primary, with a thyristor rectifier bridge. In Regavolt mode, a circuit makes the thyristors act as diodes, allowing the autotransformer to adjust output. The autotransformer remains in circuit during electronic operation, so both can adjust output simultaneously.

  • Intelligent Transformer Rectifiers

Microprocessor technology has advanced substantially, particularly in control and protection. Cathodic protection specialists use its programming, data storage and reporting capabilities to improve protection accuracy and asset life, reduce periodic field inspections and provide rapid access to data.

Intelligent cathodic protection systems are ideal for refineries, power plants, petrochemical facilities and intercity pipelines. Permanent half-cells continuously transmit structure potentials relative to the electrolyte, such as soil or water, to the transformer rectifier. The intelligent controller adjusts output current to keep all monitored points within the protection criteria. Main components are:

  • Transformer rectifier with microprocessor or microcontroller control
  • Fixed half-cells permanent reference electrodes

Intelligent transformer rectifier types include:

  • Single Reference Constant Potential Transformer Rectifiers

A single permanent reference electrode controls injected current. Continuous structure-to-electrolyte potential measurement adjusts transformer rectifier output. The controller monitors reference potential and changes pulse width and thyristor firing angle to alter current and hold the potential within protection criteria.

  • Multiple Reference Intelligent Transformer Rectifiers

Several permanent reference electrodes feed potential measurements to the control unit to regulate injected current.

The microprocessor unit has four sections:

  • Input sampling of permanent reference-electrode potentials
  • Input processing
  • Display output
  • Analogue output

The input unit receives and processes samples. The processing unit takes all samples and increases or decreases analogue output according to the half-cell potentials to bring readings to the best condition.

When half-cell potentials are within the protection criteria, output remains constant. The processor displays the required information to the user. If sample potentials change, it immediately adjusts analogue output to adapt the protection system.

RS485 serial communication allows a bus network. Transformer rectifiers are linked by a two-wire connection to one another and ultimately to a server that exchanges data and control with a computer.

Each unit has its own server address. The server initiates communication by placing the target address on the bus. All units receive it, but only the matching unit prepares to receive further data. The next signal contains a send or receive instruction, after which other commands can follow.

Borna Electronic can design and manufacture intelligent transformer rectifiers to meet customer requirements or project needs.

This arrangement provides reports on system status and reference potentials. Commands can be sent to individual units to keep reference potentials within the protection range.

Data exchange is also possible by landline where available or mobile SIM. An interface connects to the controller and transfers information and commands through a telephone connection.

Intelligent transformer rectifiers have Local and Remote modes. In Remote mode, the server controls the system; in Local mode, an operator makes adjustments at the station.

Borna Electronic can design and manufacture transformer rectifiers to meet customer requirements or project needs.