Industrial electrical networks use several earthing methods. One of the most common, because of its advantages, connects the system to earth through a neutral grounding resistor NGR.
Benefits of Neutral Grounding Resistors
An unearthed system has three drawbacks:
1. Greater faults arising from switching overvoltages

2. Two simultaneous single-phase faults can have effects equivalent to a line-to-line fault

3. A floating neutral causes phase-voltage rise and insulation damage during a single-phase fault

Installing an NGR addresses these problems and provides further benefits.
Neutral grounding resistors are used in AC networks with balanced loads and are connected between the generator or transformer neutral and earth. The network gains the benefits of earthing while limiting single-phase fault current to an acceptable level. If disconnection is delayed, the limited current avoids damage to network components because the NGR reduces it to a tolerable value.
IEEE142-1991 identifies the following benefits:
- Reduced melting and burning damage at the fault location
- Reduced mechanical stress on equipment carrying fault current
- Reduced electric-shock risk to personnel from single-phase fault currents returning to the neutral
- Reduced arcing and risk to personnel near a single-phase fault
- Reduced voltage rise on other phases during a short circuit
- Reduced transient overvoltage caused by short circuits
Resistance Earthing Methods
There are two general methods:
1. Low-resistance grounding, discussed below
2. High-resistance grounding, discussed under NGC equipment
NGR enquiries and orders must specify operating voltage, current, resistance and operating duration. Providing accessory requirements, environmental conditions and panel protection rating helps the company respond more accurately to customer needs.
Selecting NGR Ratings
TNGR selection depends on network calculations considering:
1. Maximum circuit-breaker clearing time, protection zoning, earth fault relay settings and reclosing relays; typically 10 seconds
2. Network single-line diagram, including CT ranges
3. Full details of the network component with the lowest fault-current withstand capability
4. Symmetrical three-phase short-circuit current
5. Maximum permitted network fault current
These determine the four main NGR parameters: voltage, current, resistance and operating duration.
Voltage selection generally involves calculating the maximum single-phase voltage.
When calculating current, the resistive component of single-phase fault current must not be below the combined capacitive components of the three phases; it should be approximately three times greater. Most designers use this threefold relationship.
IR=U/R ·IC=U/XC·XC=1/WC ·∑IC=3U/WC·
C can include capacitance between transformer windings and earth, cables from transformer to switchgear, outgoing feeders and other parts. It varies by network. In one company project at a 63/20 kV substation, total capacitance was 2.873 μF.
IR≥ ∑IC=> U/R≥3U/WC · R≤1/3WC∑
Also, R = VPhase / ILimited, provided this satisfies the condition above. NGR current must exceed the calculated value, but its upper limit and final selection depend on the weakest component’s current withstand and the extent of the downstream network.
Dividing voltage by current gives the NGR resistance.
Operating duration depends on fault detection and main circuit-breaker clearing times, allowing for reclosing relays. It is usually selected as 10 seconds.kers, considering reclosing relays, and is generally selected as 10 seconds.
Standards and Testing
CThe only current standard for neutral grounding resistors is IEEE32-1972, titled:
IEEE Standard Requirements, Terminology & Test Procedure for Neutral Grounding Devices
It covers all neutral earthing devices, with Section 10 specifically addressing neutral grounding resistors.
The standard specifies these NGR tests:
1. Resistance measurement under Section 4-1-10
2. Dielectric test under Section 2-3-10
Borna Electronic can perform both tests in its high-voltage laboratory.
Technical Specifications
- Environmental Conditions
Temperature −15 to +60 °C. Customers must state temperatures outside this range when enquiring.
Altitude Design allowance is up to 1000 m above sea level. Customers must state higher altitudes when enquiring.
Humidity Up to 100%
- Element Types
- Wire Wound

Wire-wound resistor with ceramic core

Wire-wound resistor with porcelain HV core
- Spring

Spring resistor
- Edge Wound

Edge-wound resistor
- Grid

Grid resistor
- Ribbon Type

Ribbon resistor
- Casting Alloy

Cast-alloy resistor
3.Panel
1. Suitable for outdoor or indoor installation
2. Protection ratings from IP23 to IP55
4.Input and Output Terminals
1. Input terminals use HV bushing insulators inside a lockable IP54 box. A suitable brass gland or aluminium gland plate is provided beneath the terminal box.
2. Output terminals use LV bushing insulators installed at the bottom of the unit.
5.Accessories
The following can be fitted to order:
- Monitoring relay for equipment continuity and earth fault detection
- Manual or motor-operated disconnector
- Current and voltage transformers if required
- Thermostat when a heater with an integral thermostat is not used
- Microswitch

