Earthing equipment is usually uncoated and can cause substantial leakage and stray currents near cathodic protection systems. This affects their operation and reduces efficiency.
Polarisation cells address this by blocking cathodic protection current while offering very low resistance to AC current flowing to earth. They resist DC flow from the cathodic protection system to the earthing system up to 1.5–2 V, but provide a path to earth during lightning or a possible short circuit on the protected structure. Installed in series between the protected structure and earthing system, they are designed for the anticipated earth-system surge current. Common surge ratings are 5, 10, 25, 50 and 100 kA.
A liquid polarisation cell consists of a PVC box containing nickel plates immersed in saturated KOH solution.
Borna Electronic can design and manufacture liquid polarisation cells to meet customer requirements or project needs.